Technical data EK5200
Task within EtherCAT system coupling of standard digital and analog EtherCAT Terminals and EtherCAT Box modules to DeviceNet networks
Number of EtherCAT Terminals depending on the process data size
Type/number of peripheral signals depending on the process data size
Protocol DeviceNet
Data transfer rates up to 500 kbaud (automatic detection)
Configuration not required
Bus interface 1 x open style connector, 5-pin, included
Power supply 24 V DC (-15 %/+20 %)
Input current typ. 120 mA + (total E-bus current)/4
Current consumption E-bus up to 2 A
Power contacts 24 V DC max./10 A max.
Electrical isolation 500 V (power contact/supply voltage/Ethernet)
Dimensions (W x H x D) 65 mm x 100 mm x 80 mm
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable